Powerlock+thru to 3x125A 3ph, 3x63A 3ph, 3x
32A 3ph & 6x16A 1ph Inc Neutral Protection
Input:
400A Powerlock protected by 400A 4P MCCB
Output:
400A Powerlock with unprotected link through
3 x 125A/3 protected by 3 x 125A 4P MCB with VT/VS RCD with switch disable
3 x 63A/3 protected by 3 x 63A 4P MCB with VT/VS RCD with switch disable
3 x 32A/3 protected by 3 x 32A 4P MCB with VT/VS RCD with switch disable
6 x 16A/1 protected by 6 x 16A 30mA RCBOs